1.AC current source (3 * 30A)
Single phase current output (RMS) |
0 -- 30A / phase, accuracy: 0.2% ± 5mA |
Three phase parallel output (RMS) |
0 -- 90A / three phase in phase parallel output |
Allowable working value of phase current for a long time (effective value) |
10A |
Maximum output power per phase |
300VA |
Maximum output power of three phase parallel current |
800VA |
Maximum output allowable working time of triple parallel current |
5s |
frequency range |
0 -- 1000Hz, accuracy 0.001Hz |
Harmonic number |
2--20second |
phase |
0--360The accuracy is 0.1 degree |
2.DC current source
DC current output |
0--± 10A / phase, accuracy: 0.5% ± 5mA |
3.AC voltage source
Single phase voltage output (RMS) |
0 -- 120V / phase, accuracy: 0.2% ± 5mv |
Line voltage output (RMS) |
0--240V |
Phase voltage / line voltage output power |
75VA/100VA |
frequency range |
0 -- 1000Hz, accuracy: 0.001Hz |
Harmonic number |
2--20second |
phase |
0--360Degree, accuracy: 0.1 degree |
4.DC voltage source
Single phasevoltage output amplitude |
0--± 160V, accuracy: 0.2% ± 5mv |
Output amplitude of line voltage |
0--±320V |
Phase voltage / line voltage output power |
90VA/180VA |
5.Switching value terminal
Switch input terminal |
8yes |
Air contact |
1 -- 20 mA, 24 V, internal active output of the device |
Potential reversal |
Passive contact: low resistance short circuit signal Active contact: 0-250V DC |
Switch output terminal |
4Yes, no contact, breaking capacity: 110V / 2a, 220V / 1a |
6.Others
time frame |
1ms -- 9999s, measuring accuracy: 1ms |
Volume and weight of portable series single machine |
Volume 328 x 168 x 250mm3, about 12.5kg |
Power Supply |
AC110V±10%,60Hz,10A |