To select the right specifications,please provide the following technical parameters
1.Power transformer:voltage level,large capacity,testing nature(neutral point withstand voltage or full insulation withstand voltage),single phase to ground electrical capacity;
3.Generators and motors:voltage level(outlet voltage or working voltage),test voltage(withstand voltage value),single phase to ground electrical capacity range(such as 0.2-0.55uF,etc.);
4.Switches,insulators,PT,CT,insulation tools,busbars:voltage level(or working voltage);Test voltage(withstand voltage value);
5.CVT validation:voltage level or working voltage,test voltage(withstand voltage),capacitance range(such as 0.005-0.02uF).
HMCXZ-135kVA/108kV Variable Frequency AC Resonant Test System
1、Applicable scope
1.AC withstand voltage test of 35kV/300mm2 cable 1km,capacitance≤0.1945uF,test frequency 30-300Hz,test voltage 52kV,test time 60 minutes.
2.AC withstand voltage test of 35kV main transformer,capacitance≤0.015uF,test frequency 45-65Hz,test voltage not exceeding 75kV,test time 1 minute.
3.10kV/300mm2 cable 3km AC withstand voltage test,capacitance≤1.1265uF,test frequency 30-300Hz,test voltage 22kV,test time 5 minutes.
4.AC withstand voltage test for 35kV switches and transformers,with a test frequency of 30-300Hz,a test voltage not exceeding 100kV,and a test time of 1 minute.
5.AC withstand voltage test of 10kV main transformer,capacitance≤0.015uF,test frequency 45-65Hz,test voltage not exceeding 50kV,test time 1 minute.