- Lithium battery pack: 24V/5AH;
- Synchronization: external synchronization AC10~380V, with virtual synchronization function; wireless synchronization AC10~380V;
- Display interface: true color, viewing area 152×92mm, resolution 800×480;
- System platform: WinCE6.0, 1 network port, 1 USB port, support flash drive;
- Weight: 236×177×53mm, about 1.5Kg;
- Use environment: temperature -10 ~ 55 ℃, humidity RH90% or less.
Details specification
1. Contact AE PD detection
Detection frequency band: 10kHz~300kHz;
Detection sensitivity: ≤10pC;
Linearity error: ≤±10%;
Stability error: ≤±5%;
Dynamic range: ≥60dB;
Gain: 0~60dB;
Signal acquisition: 16bit, 10MS/s;
Measurement range: 0~80dB;
2. Non-contact AE PD detection
Detection frequency band: 10kHz~300kHz;
Center frequency: 40kHz;
Detection sensitivity: ≤10pC;
Linearity error: ≤±10%;
Stability error: ≤±5%;
Dynamic range: ≥60dB;
Gain: 0~60dB;
Signal acquisition: 16bit, 10MS/s;
3. UHF PD detection
Working frequency band: 300M~1500MHz;
Detection sensitivity: ≤0.1pC;
Average effective height: ≥11mm;
Stability error: ≤±5%;
Dynamic range: ≥60dB;
Signal acquisition: 16bit, 250MS/s;
4.HF PD detection
Detection frequency band: 3MHz~30MHz;
Detection sensitivity: ≤5pC;
Transmission impedance: ≥5mV/mA;
Linearity error: ≤±3%;
Stability error: ≤±5%;
Dynamic range: ≥60dB;
Gain: 22dB~72dB;
Signal acquisition: 16bit, 250MS/s;
5.Transient ground voltage PD detection
Working frequency band: 3M~100MHz;
Gain: 0~60dB;
Minimum discharge capacity: ≤10pC;
Pulse counting error: ≤5%;
Positioning accuracy: 30cm;
Linearity error: ≤±3%; Stability error: ≤±5%;
Dynamic range: ≥60dB;
Signal acquisition: 16bit, 250MS/s;