1. Name
Digital detection system of Partial Discharg
2. Power Supply
220V AC-5%to+10%Freq:50Hz±5%
3. Environment
①Temperature:-5℃~40℃
②Humidity:<85%
4. Security
①Insulation resistance:>2MΩ
②Leakage:<3.5mA
③Dielectric strength:the power line right into
the chassis can withstand 1500V(50HZ RMS)1min
of the voltage test.
5. Shape and weight
①size:300x350x90(mm)
②weight:4kg
6. Host function index
①CH:4;
②Sensitivity:0.1pc;
③Measurement band:3dB bandwidth of
10kHz-1000kHz Multi-file any combination;
Lp:10K、20K、40K,80K;
Hp:100K、200K、300K,1000K;
④Gain Range:-20 dB∽+40 dB fourth gear can be coarse to fine-tune;