1. Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847
2. Power supply: AC220V±10%, 50Hz/60Hz±10%
3. Power output: 0.1~125V (AC)
4. Current output: 0.001~5A(RMS)
5. Power output: 300VA
6. Maximum knee voltage measurement: 45kv
7. Current measurement:
Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
Error: <±0.1%+0.01%FS
8. Voltage measurement:
Range: 0~200 V (automatically change range in 1V/10V/70V/200V)
Error: < ±0.1%+0.01%FS
9. Turns ratio measurement:
Range : 1~30000,
1~1000 error<0.05%
1000~2000 error<0.1%
2000~30000 error<0.2%